Y-type cast iron strainer for pipes (English Version)
Performance parameters | General installation requirements | Special specifications for fire protection systems |
---|---|---|
Pressure rating | PN6-PN40 | PN16-PN25 |
Impact flow velocity | 4.5m/s for DN300 and below/3m/s for DN350-600 | |
Coating specifications | Blue anti-corrosion coating | Red special coating |
Wall thickness calculation formula takes into account both fluid mechanics and casting process requirements:
Inspection type | Required inspection items | Judgment criteria |
---|---|---|
Type test | Overpressure strength test | 4 times CWP pressure stabilization for 15 minutes |
Factory inspection | Sealing test | 1.25CWP pressure maintenance for 2 minutes |
A DN400 water plant project uses the double insurance configuration of the