Analysis of the core content of the standard
Technical dimensions | Core requirements | Typical parameters |
Functional requirements | Data acquisition/processing/remote transmission, remote control, time synchronization | Support 6 protocols including DL/T860 |
Performance indicators | Response time, communication capacity, reliability | Remote signal response ≤200ms, MTBF ≥30000h |
Electromagnetic compatibility | 10 types of immunity test | Electrostatic discharge level 4 (8kV) |
Detailed explanation of key technical requirements
1. Communication architecture design
The gateway needs to adopt a dual network redundant architecture, support 255 IED access, and have:
- Multi-master station communication of DL/T634.5104 and other protocols
- Automatic channel switching (switching time ≤10s)
- IRIG-B timing accuracy <1ms
2. Security protection mechanism
The standard emphasizes:
Case: Remote control operation must be authenticated by a digital certificate, and the operation log records complete fields including operator, object, time, result, etc., with a storage period of ≥1 year
Implementation recommendations
Key points for acceptance testing
- Performance verification: Simulate 200-point/second remote signal impulse test
- Protocol compatibility: Need to test the quality code conversion between DL/T860 and IEC62361-2
- Environmental adaptability: -40℃~70℃ temperature gradient test
Standard evolution analysis
Compared with the old version, the 2021 version adds:
- Remote browsing function (CIM/VG graphic standard)
- Oscillating wave immunity test requirements
- RCD configuration file format specified in Appendix C